Bently Nevada 330930-065-01-05 Extension Cable
Bently Nevada 330930-065-01-05 Extension Cable
The Bently Nevada 330930-065-01-05, also cataloged as the 330930 Extension Cable, operates as a dedicated hardware component for proximity probe signal transmission within the 3300 XL NSv Proximity Transducer System.
Suffix Breakdown & Model Matrix
- 330930: 3300 XL NSv Extension Cable
- 065: Cable length of 6.5 m (21.3 ft)
- 01: Stainless steel armor with FEP jacket
- 05: FluidLoc® cable option (axial seal preventing fluid leakage along cable)
Hardware Specifications
| Parameter | Specification |
|---|---|
| Model | 330930-065-01-05 |
| Brand | Bently Nevada |
| Origin | Not specified |
| Weight | Not specified |
| Dimensions | Cable length 6.5 m (21.3 ft) |
| Operating Temp | -51 deg C to +177 deg C |
| Power Consumption | Passive coaxial cable |
| System Compatibility | 3300 XL NSv Proximity Transducer System |
| Connector Type | Miniature coaxial, gold-plated center contact |
| Maximum Cable Length | Must match Proximitor calibration (5.0 m or 7.0 m total) |
| Armor Material | Flexible stainless steel with FEP jacket |
| Environmental Limits | 100% condensing humidity, non-submerged with protected connectors |
Eddy-Current Probe Scaling and Rotor Dynamics
The extension cable maintains calibrated eddy-current probe scaling across NSv systems. Controlled impedance ensures gap voltage validation at -10 VDC reference points. FluidLoc® sealing prevents axial fluid migration, preserving rotor dynamics monitoring integrity. Stainless steel armor stabilizes shielding continuity, suppressing cross-talk between adjacent coaxial runs.
Frequently Asked Questions
Q: Can the 330930-065-01-05 be used in submerged environments? A: No. It is rated for 100% condensing humidity but not continuous submersion.
Q: Does FluidLoc® sealing affect impedance? A: No. FluidLoc® provides mechanical sealing only; electrical characteristics remain unchanged.
Q: How does cable length affect calibration? A: Probe, cable, and Proximitor must match factory-defined lengths. The 065 option is intended for 7.0 m total system configurations.
Field Installation Guidelines
- Maintain minimum bend radius: 25.4 mm unarmored, 30.5 mm armored.
- Bond shielding at the Proximitor end only to avoid ground loops.
- Protect connectors from fluid ingress; FluidLoc® provides axial sealing but not external connector sealing.
- Route away from high-current conductors to minimize electromagnetic interference.
- Verify total system length compliance before energizing the transducer system.
Bently Nevada 330930-065-01-05 Extension Cable