Vendor: Honeywell

Honeywell 900B16-0202 Analog Output Module

SKU: 900B16-0202
In stock
Description

Honeywell 900B16-0202 Analog Output Module

The Honeywell 900B16-0202, also cataloged as the 900B16-0202 Analog Outputs 0 to 20 mA, operates as a dedicated hardware component for multi-channel current signal transmission within HC900 controller systems.

Hardware Specifications

Parameter Specification
Model 900B16-0202
Brand Honeywell
Origin USA
Weight 2 kg (shipping)
Dimensions Rack-mounted form factor (HC900 cabinet)
Operating Temp 0 to +60 deg C
Power Consumption 5 V; 350 mA max / 24 V; 700 mA max
Core Function 16 analog outputs, 0 to 20 mA, isolated in 4 groups
Accuracy 0.1% full scale at reference conditions
D/A Resolution 13+ bits (1 part in 13332)
Isolation 500 VDC group-to-group, 500 VDC from logic
Load Resistance 750 ohms max
Calibration Redundant factory calibration, field calibration per channel
Diagnostics Monitoring of calibration and configuration
Output Verification Feedback to controller to confirm current flow

4-20 mA HART Loop Protocol

The module supports integration into HC900 systems where 4-20 mA HART loop protocol is utilized for process control. Channel grouping ensures channel-to-channel isolation, reducing interference across redundant outputs. Calibration data stored in non-volatile memory allows consistent diagnostics and rejection of invalid calibration versions.

Frequently Asked Questions

Q: Can the 900B16-0202 module be hot-swapped during operation? A: Modules are not designed for hot-swap; power-down is recommended before insertion or removal.

Q: How does the rack limit module count with this output card? A: A maximum of 2 modules per rack is supported when powered from internal 24 V backplane supply.

Q: What is the redundancy behavior of calibration data? A: Factory calibration is stored redundantly; invalid versions are automatically rejected, ensuring valid channel operation.

Field Installation Guidelines

  • Use the designated 36-position Euro style terminal block (900TCK-0001) for wiring.
  • Maintain shielded cable grounding at a single point to minimize noise coupling.
  • Segregate analog signal wiring from digital or high-voltage lines.
  • Ensure proper airflow around modules to prevent localized heating.
  • Verify load resistance does not exceed 750 ohms per channel to maintain accuracy.
  • Perform field calibration per channel after installation to align with process requirements.